Standards and grid connection
Demand Connection Code (DCC)
The Demand Connection Code (DCC) is a European network code setting out technical requirements for the connection of large power-consuming installations and closed distribution systems (CDS). Without conclusive simulation data and a compliance statement, you are not permitted to commission new high-power consumers, such as motors, electric boilers or charging stations. We measure, simulate and assess your installation against the DCC and advise on the necessary measures.
This article comprises 10 sections
In brief
- What
- A European grid code setting out requirements for the connection of large, new electricity consumers.
- Consequence
- Without an approved simulation report, the network operator will refuse your new or upgraded connection.
- Cause
- Non-linear loads such as variable frequency drives, LEDs and solar panels distort the voltage beyond the permitted limits.
- Approach
- Have voltage quality, reactive current and frequency response calculated during the design phase and demonstrate that you remain within the P-Q window.
What is the Demand Connection Code?
The DCC is a set of harmonised European rules for large-scale consumer installations and closed distribution systems. Previously, each network operator had its own requirements; the DCC standardises these into a single set of rules. It does not apply to every consumer, but to organisations with a large, complex installation or their own closed distribution system (GDS).
The code sets requirements for power quality at the point of transfer with the network operator. It is aligned with standards such as EN 50160, which specifies the limits for voltage characteristics.
- Harmonic distortion. Limits on the distortion caused by your installation, such as a THDu of no more than 8 per cent.
- Voltage variations. No unacceptably rapid voltage drops or surges, for example due to high inrush currents.
- Flicker. Limits on rapid variations that cause lighting to flicker, measured in Pst and Plt.
- Reactive power. Limits on the reactive power you exchange with the grid.
Think of the grid as a busy motorway. Every vehicle must comply with technical requirements and speed limits. A heavy goods vehicle that keeps changing lanes and is leaking oil causes traffic jams and accidents. The DCC is the MOT and the traffic regulations that prevent your installation from disrupting the flow of traffic.
Why the DCC also protects your installation
The DCC does not merely protect the network operator. Compliance with the code is directly linked to the health of your own installation.
- Disconnection. In the event of systematic breaches of emission limits, the network operator may intervene and, in extreme cases, disconnect the supply.
- Fire hazard. High harmonic currents heat up cables, neutral conductors and transformers. This accelerates ageing and increases the risk of fire.
- Costs. A low cos phi results in unnecessary reactive power transmission, leading to additional transmission costs or reactive power penalties.
- Damage to equipment. PLCs and variable frequency drives are sensitive to voltage fluctuations and distortion. An installation that does not meet the required standards will cause its own faults.
How to recognise it
- Sensitive protection devices: Earth leakage circuit breakers or automatic circuit breakers trip without a severe short circuit.
- Heat and vibrations: Transformers or motors become hot (visible via thermography), vibrate or hum loudly.
- Flickering lights: Rapid voltage fluctuations caused by switching on heavy loads.
- Faultycapacitors: Capacitor banks frequently fail due to excessive harmonic voltages or resonance.
- Data and communication loss: Networks fail or measurement and control equipment malfunctions.
Enabling you to push the boundaries
This is almost always due to the replacement of linear equipment with power electronics. LEDs, solar panels and variable frequency drives draw current in short spikes rather than a smooth waveform, thereby distorting the voltage. If the grid impedance at the connection point is high, or if many non-linear loads are operating simultaneously, the distortion quickly rises above the limits set by EN 50160 and the DCC.
Example:A company adds packaging lines fitted with heavy-duty variable frequency drives. Shortly afterwards, PLCs reset and the grid operator reports that emission limits have been exceeded. Continuous waveform recording shows a THDu of 9.5 per cent, above the 8 per cent limit. An active harmonic filter connected in parallel to the distribution board reduces the THDu to 3 per cent. The PLCs are working again and the installation now complies with requirements.
What you can do
-
Structural design and settings
- Distributing phases. Smartly distributing single-phase loads across the three phases reduces asymmetry and neutral currents.
- Staggered start-up. Starting heavy-duty motors one after the other prevents severe voltage dips and flicker.
-
Passive measures: filtering and detuning
- For constant, predictable distortion, a passive harmonic filter.
- Detuning existing capacitor banks using chokes to prevent resonance.
-
Active solutions for variable loads
- A Static Var Generator (SVG) compensates for reactive power quickly and continuously, without the risk of resonance.
- An active harmonic filter injects a counter-current and restores the sine wave.
Please note:Never simply installstandard capacitor banks in a network with high levels of harmonics. Without prior tuning or network analysis, resonance can exacerbate distortion and cause components to fail.
This depends on your connection and the associated requirements. Our engineers will carry out measurements, simulate the extension and check it against the code.
Common mistakes
- Holding the network operator to accountThe network operator monitors quality up to the meter. You are responsible for what your installation feeds into the grid.
- Relying on CE markingA single device may be sufficient, but dozens of CE-marked inverters operating together often still exceed the emission limits.
- Viewing a UPS as a total solutionA UPS protects against power failures, but often does not filter out internal harmonics.
- Expanding without a baseline measurementWithout knowledge of the network impedance, adding additional equipment often leads to resonance and tripping of protective devices.
- Tackling the symptomsReplacing faulty variable speed drives without investigating power and voltage quality is a waste of capital.
Five steps to a DCC-compliant installation
- Identifying failure behaviour
How often do processes shut down, do components overheat, or do residual current devices trip?
- Measurement
Continuous waveform recording using power quality analysers, for a minimum of one week.
- Tests
Compare THDu, Pst and reactive power with the DCC and EN 50160.
- Solutions
From phase balancing to an active harmonic filter.
- Check
Carry out further measurements to demonstrate that the installation complies.
When should you call in an engineer?
Standard multimeters do not accurately detect rapid dips and harmonics. It is advisable to speak to a HyTEPS engineer:
- If you receive a notification that your installation’s emissions are too high.
- Before undertaking a major expansion, such as electrification, installing numerous charging points, heat pumps or solar panels, have the impact on power quality simulated in advance.
- When frequency converters, power supplies or capacitor banks continue to fail without short-circuiting or overloading.
A similar grid code applies to generation installations: the Requirements for Generators.
Frequently asked questions
Will my installation comply if I stay within the NEN-EN 50160 standard?
Not necessarily. The standard sets out the minimum requirements at the grid operator’s transfer point. Modern equipment may be more sensitive and could malfunction, even if the voltage falls within the standard. We therefore assess the compatibility between your power supply and your load.
Why are my protections tripping when I don't seem to be overloaded?
This is known as nuisance tripping. Often, it is not the total current that is the cause, but its distortion (harmonics) or brief current spikes that your measuring equipment fails to detect. These cause thermal protection devices to overheat or disrupt electronic protection devices. A measurement reveals why a protection device is tripping.
How long does a typical Power Quality survey take?
To obtain a reliable picture, we usually carry out measurements over a period of at least one to two weeks, so that a full operating cycle, including weekends and peak loads, is recorded. In the event of acute faults, we can also carry out short-term measurements or utilise continuous waveform recording.
What is the next step after an analysis?
You will receive a report containing conclusions in plain language alongside the technical details. Where necessary, we simulate the solutions so that you know in advance how a particular measure will perform. We then oversee the implementation and verify the result with a follow-up measurement.
Read more
Have your installation assessed by an engineer
You’ll receive a reply within one working day. Your first consultation will be with an engineer.