Symptoms · Voltage
Voltage imbalance
Voltage imbalance occurs when the three phases are no longer of equal magnitude or are not exactly 120 degrees apart. You may notice this in motors that overheat and fail more quickly, a neutral conductor carrying current, and circuit breakers tripping even though the load appears to be within limits. We measure the imbalance per phase, determine whether the source lies within your installation or in the grid, and advise on the appropriate course of action.
This article comprises 10 sections
In brief
- What
- In a three-phase network, the phase voltages are unequal in magnitude, or the phase angle deviates from 120 degrees.
- Consequence
- Motors and transformers must no longer be operated at full load (derating), and high currents are flowing in the neutral conductor.
- Cause
- This is usually caused by an uneven distribution of single-phase loads, such as lighting or IT equipment, or a fault in the supply network.
- Approach
- Redistribute loads, install an active harmonic filter for load balancing, or consult the network operator if the cause is external.
What is voltage imbalance?
Voltage imbalance, also known as voltage asymmetry, means that in a three-phase system, the RMS values of the phase voltages L1, L2 and L3 are not equal, or that the phase shifts deviate from the ideal 120 degrees.
- Ideal
- 3 ×120°: Three equal voltages, exactly 120 degrees apart.
- Boundary
- 2% in public low-voltage networks, over 10 minutes, 95% of the week.
- Standard
- EN 50160:In industry, IEC 61000-2-4 may be more stringent for Class 1.
Think of it as three horses pulling a heavy cart. If they are equally strong and move in unison, the cart will travel straight ahead. If one horse is weaker or pulls in a different direction, the other two have to work harder and the cart will swerve. Energy is lost through friction and the need to correct the course.
For engineers: symmetrical components. According toFortescue’s theory, imbalance introduces a negative sequence into the voltage field. In an electric motor, this generates a counteracting torque: the motor attempts to rotate forwards and backwards at the same time. This results in no movement, only heat.
The cost of imbalance
The installation usually continues to operate, which is why imbalance is often underestimated. However, efficiency and safety are significantly reduced.
- Overheated motors and transformers. A voltage imbalance of just 2% can result in a current imbalance of 15 to 20% in the windings of an induction motor. Every 10 °C rise in temperature halves the service life of the insulation; a motor running continuously at a 3 per cent imbalance will fail prematurely. To prevent this, you must derate the motor: a 100 kW motor may only be loaded to 85 kW.
- An overloaded neutral conductor. In a balanced circuit, no current flows through the neutral. In the event of an imbalance, however, it does. The neutral conductor is often not fused and is sometimes thinner than the phase wires: at high currents, it becomes overheated, posing a fire hazard.
- Damage to power electronics. Frequency converters and inverters have rectifier bridges at their input. In the event of an imbalance, one phase supplies the majority of the current; these diodes become overloaded and the drive goes into fault mode or fails.
How to identify imbalance
- Vibrations and humming: Motors and transformers are making more noise than usual.
- Uneven temperature: One phase cable is noticeably warmer than the other.
- Neutral current: A high current in the neutral conductor, even when there are few third-harmonic components.
- Tripping protection devices: Motor thermalprotection devices trip, even though the total load appears to be within specifications.
What causes imbalance?
- Unevenly distributed single-phase loads are the most common cause. If lighting, PCs, servers and small motors are all connected to L1, the voltage on L1 drops, whilst L2 and L3 remain relatively high.
- Faults in the grid. A faulty capacitor bank, a poor connection in a transformer or a blown fuse in a single phase immediately causes a serious imbalance.
- Asymmetrical impedance. Sometimes the cabling itself is the cause, such as untwisted cables over long distances or rail systems with uneven geometry.
What you can do about it
Start by gaining insight. Replacing reactive components is pointless.
-
Phase reallocation is the most cost-effective solution
- Identify which single-phase loads are connected to which phase, and move groups of loads from the heaviest-loaded phase to the least-loaded phase. This requires accurate current measurement per phase.
-
Active harmonic filter – structural
- An active harmonic filter not only filters harmonics but can also be configured for load balancing. It measures the current per phase and injects current from the other phases to restore balance.
- This reduces the load on the supply transformer and draws current from the neutral conductor upstream of the filter.
-
Motor protection and safety
- Phase voltage monitoring relays switch off the motor as soon as the imbalance exceeds a critical threshold, for example 3% or 5%. This prevents burnt-out windings.
Read more about engineering.
Our engineers carry out phase-by-phase measurements and assess the available options.
Common mistakes
- Measuring only the average currentAt 100 A, 100 A and 160 A, an average of 120 A seems acceptable, but phase 3 is heavily overloaded. Always check each phase individually.
- Attributing zero-sequence current to harmonicsImbalance causes zero-sequence current at least as often as the 3rd harmonic. A power quality analysis makes the distinction.
- Ignoring deratingRunning a motor at the limit when there is an imbalance is asking for trouble. Follow the NEMA derating curve strictly.
- Looking for the cause outside the premisesThe incoming voltage is a factor, but the majority of problems stem from the distribution within the installation.
- Confusing voltage and currentA small voltage imbalance results in a significant current imbalance, and that is what causes the damage.
From diagnosis to solution
- Measurement
Take measurements on the main or sub-distribution board for at least a week. A single snapshot is insufficient, as the load varies.
- Analysing the currents
Is there a clear difference between L1, L2 and L3?
- Analysing the voltage
Is the voltage imbalance greater than 1 to 2 per cent?
- Checking the neutral current
Is there current flowing in the neutral when the load is low?
- Assessment
Which major single-phase loads have been added recently?
- Take action
Can phases be reversed? If not, consider an active filter.
When should you call in an engineer?
Sometimes, changing the phase group is not possible or is insufficient. It is advisable to speak to a HyTEPS engineer if:
- critical processes fail and the cause is unclear;
- if you are planning a major expansion, such as installing heat pumps or charging points, and want to know whether your transformer can cope with this in terms of balance;
- If you are unsure whether your measurements are being interpreted correctly, we also record transients and waveforms using continuous waveform recording;
- if you want to tackle unbalance, harmonics and reactive power all at once.
Frequently asked questions
Is installing an Active Harmonic Filter always the solution?
No. A filter is a powerful tool, but not a miracle cure. Sometimes the solution lies in adjusting the transformer settings, redistributing loads or re-routing cabling. That is why a thorough analysis and simulation should be carried out first, followed only then by any necessary hardware modifications.
Why are my protections tripping when I don't seem to be overloaded?
This is known as nuisance tripping. The cause is often not the amount of current, but its distortion (harmonics) or brief current spikes that your meters fail to detect. These cause thermal protection devices to overheat or confuse electronic protection devices. A targeted measurement reveals why a protection device is tripping.
Will my installation comply if I stay within the NEN-EN 50160 standard?
Not necessarily. The standard sets out the minimum requirements at the grid operator’s transfer point. Modern equipment may be more sensitive and could malfunction, even if the voltage falls within the standard. We therefore assess the compatibility between your power supply and your load.
How long does a typical Power Quality survey take?
To obtain a reliable picture, we usually carry out measurements over a period of at least one to two weeks, so that a full operating cycle, including weekends and peak loads, is recorded. In the event of acute faults, we can also carry out short-term measurements or utilise continuous waveform recording.
Read more
Have your installation assessed by an engineer
You’ll receive a reply within one working day. Your first consultation will be with an engineer.